Deciding the area of cable for starting submersible motor pump in condition of far distance between the transformer and motor |
ZHANG Xian-liang, LING Gui-rong |
Hengyang Xiangnan Motor Works, Hengyang, Hunan 421001, China |
|
|
Abstract In condition of far distance between the transformer and submersible motor pump,it needs a long cable to connect the both,which causes a large voltage drop and thus leads to unsuccessful submersible motor start.By analyzing the start torque,start current,and start voltage,we derived formulas to calculate the needed minimum area of cable and to calculate the maximum length of cable at certain area of cable for normally starting the motor.The example is given out to illustrate that the needed minimum area of cable is in proportion with rated current IN,the length of cable L,and inverse proportion rated voltage UN.These formulations can also be applied when connecting general motor with centrifugal pump.submersible motor;submersible motor pump;line voltage reduce;start torque;start voltage;needed minimum area of cable
|
Received: 08 August 2013
|
|
|
|
[1] 张东升.线路压降对泵站电机起动的影响[J].排灌机械,1992,10(1):46-48[2] 张翼飞.离心泵的起动特性分析[J].排灌机械,1996,14(4):6-9[3] 吴建平,鲁求荣.小型潜水电泵在喷泉水景的应用[J].排灌机械,2005,23(2):29-31[4] 杨懿,金成.小型潜水电泵安全标志及内容探讨[J].排灌机械,2006,24(1):44-45[5] 孙建设,张惠敏.水泵电机的全压起动及保护技术[J].电机与控制应用,2006,33(8):55-58[6] 许实章.电机学[M].北京:机械工业出版社,1981[7] 关醒凡.现代泵技术手册[M].北京:宇航出版社,1995 |
|
|
|