Analysis of Vibration in Vertical Asynchronous Motor in Circulating Supply-Water Pump Station |
QIAN Li-hua |
Jiangdu Pump Station of Jiangsu Province, Jiangdu, 225200, China |
|
|
Abstract Aiming at the problem of vibration in vertical asynchronous motor in circulating supply-water pump station,which set in the Second Electrical Power Company Limited of Yangzhou,some reason are analyzed,such as installation,inspection and manufacture.The conclusion is obtained that the vibration is electromagnetic vibration by spectrum analysis.The vibration is fade to 0.01mm by adding 3 equalizing cable on the stator coil.
|